| Notes |
| Date |
Text |
| 2012-11-01 08:50:52 | BUILDING REVIEW APPROVED WITH PROVISO AS AGREED WITH | | | MICHAEL RETINO OVER THE PHONE ON 11/1/12: | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR ROOF SHINGLES. THERE IS NOT PRODUCT | | | APPROVAL ON PACKAGE SUBMITTED. | | | | | | 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) PRODUCT APPROVAL AS REQUIRED | | | BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. | | | | | | 3- REVISED SHEET A-6: THERE ARE DIFFERENT TYPES OF | | | NAILS SPECIFIED FOR ROOF SHEATHING. SEC. R803.2.3.1 | | | REQUIRES MIN. 8D RING SHANK NAILS. REVISE AS REQUIRED | | | OR PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING THAT | | | OTHER SPECIFIED NAILS ARE EQUAL OR BETTER THAN 8D RING | | | SHANK NAILS. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. | | | |
|