| Plan Review Notes For Permit 12090473 |
| Permit Number |
12090473 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-25 08:37:44 | 12090473 | | | 312 PURITAN ROAD | | | SFD REMODEL | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | THE GUEST HOUSE REQUIRES A GROUNDING ELECTRODE. NEC | | | 250.32 | | | | | | THE ELECTRIC SUBPANEL AT THE GUEST HOUSE MAY NOT BE | | | LOCATED IN A CLOSET. PANELS SHALL BE PLACED SO AS TO | | | REDUCE TO A MINIMUM THE PROBABILITY OF COMMUNICATING | | | FIRE TO ADJACENT COMBUSTIBLE MATERIALS. OVERCURRENT | | | DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY | | | IGNITABLE MATERIAL. SUFFICIENT ACCESS AND WORKING SPACE | | | IS REQUIRED AT THE SUB PANEL. 36"X 30? IN WIDTH IS THE | | | MINIMUM REQUIRED FOR SUB PANELS. NEC 408.17, 240.24 | | | (D), 110.26 (A) | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|