Plan Review Notes
Plan Review Notes For Permit 12090473
Permit Number 12090473
Review Stop E
Sequence Number 1
Notes
Date Text
2012-09-25 08:37:4412090473
 312 PURITAN ROAD
 SFD REMODEL
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 THE GUEST HOUSE REQUIRES A GROUNDING ELECTRODE. NEC
 250.32
  
 THE ELECTRIC SUBPANEL AT THE GUEST HOUSE MAY NOT BE
 LOCATED IN A CLOSET. PANELS SHALL BE PLACED SO AS TO
 REDUCE TO A MINIMUM THE PROBABILITY OF COMMUNICATING
 FIRE TO ADJACENT COMBUSTIBLE MATERIALS. OVERCURRENT
 DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY
 IGNITABLE MATERIAL. SUFFICIENT ACCESS AND WORKING SPACE
 IS REQUIRED AT THE SUB PANEL. 36"X 30? IN WIDTH IS THE
 MINIMUM REQUIRED FOR SUB PANELS. NEC 408.17, 240.24
 (D), 110.26 (A)
  