2012-09-26 13:15:27RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF ASSEMBLY TO BE INSTALLED. AND, CLEARLY
 IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. PROVIDE THE RAS 117 CALCULATIONS AS REQUIRED
 BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
 NEED CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 ***NOTE: IF GENERAL LIMITATION #7 REQUIRES SIGNED AND
 SEALED RAS 117 CALCULATIONS, THEN, NEED TO PROVIDE
 SIGNED AND SEALED CALCULATIONS.
  
 B) ALL USP STRUCTURAL CONNECTORS SPECIFIED BY THE
 ARCHITECT ON THE PLANS/DETAILS AND SECTIONS.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 4- ARCHITECT'S PLANS AND ENERGY CALCULATIONS NEED TO
 MATCH AND BE COORDINATED. ENERGY CALCULATIONS CALL FOR
 VENTED UNDER ATTIC, WHILE ARCHITECT'S PLANS DON'T SHOW
 ANY VENTILATION. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 5- ARCHITECT TO CLARIFY IF DESIGNING UNVENTED ATTIC.
 SEE SEC. R806.1. AND SEE SEC. R806.4 FOR REQUIRED
 CONDITIONS FOR UNVENTED ATTIC AND REVISE PLANS AS
 REQUIRED TO COMPLY.
 ***NOTE: WALL SECTION 2/8 ON SHEET A-8 SHOWS AIR
 HANDLER UNIT IN DROPPED CEILING. COORDINATE LOCATION OF
 INSULATION TO COMPLY WITH THE VENTED OR UNVENTED ROOF
 AS DESIGNED BY THE ARCHITECT.
  
 6- WALL SECTION 1/7 AND DETAIL 2/10 ON SHEET A-7 SHOW
 RECESSED R-30 INSULATION ON 2X12 ROOF RAFTERS. CLARIFY
 IF ROOF IS BEING DESIGNED AS UNVENTED. SEE ITEM #5
 ABOVE. ALSO, CLARIFY HOW MUCH IS THE INSULATION
 RECESSED. R-30 BUTT INSULATION IS ABOUT 9 1/2" THICK.
 IF THE THICKNESS IS REDUCED THEN THE R-VALUE NEEDS TO
 BE BE REDUCED ACCORDINGLY. AND, IT MAY NOT COMPLY WITH
 THE ENERGY CALCULATIONS. COORDINATE WITH ENERGY
 CALCULATIONS AND REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 ***NOTE: THIS APPLIES TO NEW BATHROOM FLAT ROOF ALSO.
  
 7- REVISE NAIL TYPE AND SPACING ON ROOF SHEATHING NOTE
 ON SHEET A-10. ROOF SHEATHING TO BE MIN. 8D RING SHANK
 NAILS AND THE SPACING FOR ROOF ZONE #3 IS 4" O.C.. SEE
 SEC. R803.2.3.1 AND REVISE AS REQUIRED.
 ***NOTE: RAS 150 IS NO ADOPTED BY THE CITY OF WEST PALM
 BEACH, THEREFORE CAN'T BE USED.
  
 8- SHEET A-1: REVISE SITE PLAN NOTE L. REMOVE EXISTING
 GARAGE NOT SHED. THIS NEEDS TO BE CLEAR BECAUSE
 DEMOLITION OF A GARAGE VS A SHED HAVE AN IMPACT ON THE
 ZONING REQUIREMENTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- SHEET A-3: BATHROOM ADDITION FLOOR FRAMING PLAN.
 PROVIDE SPECIFICATIONS FOR PROTECTION OF THE WOOD
 FRAMING MEMBERS AS REQUIRED BY SEC. R317 OF 2010
 FBC-RESIDENTIAL.
  
 10- PARTITION 42 DETAIL ON SHEET A-5 SPECIFIES "RAFTER
 DESIGNED BY REGISTERED PROFESSIONAL ENGINEER". PROVIDE
 ENGINEER DESIGN. SEC. 107.2.1 CITY AMENDMENTS.
  
 11- REVISE ENERGY CALCULATIONS SUBMITTED. SEC.
 103.2.1.1.1 FBC-ENERGY CONSERVATION.
 A) BATHROOM ADDITION IS NOT ON CONCRETE SLAB. ONLY THE
 GUEST BEDROOM IS. SEE PLANS AND REVISE AS REQUIRED.
 REVISE SQUARE FOOTAGE ACCORDINGLY.
  
 B) REVISE ITEM #10. COORDINATE WITH ARCHITECT TYPE OF
 CEILING. VENTED OR UNVENTED. SEE ITEM #5 ABOVE.
  
 C) COORDINATE ITEM # 13 WITH REVISED A/C EQUIPMENT
 SIZING CALCULATIONS AND A/C PLANS. SEE MECHANICAL
 REVIEW COMMENTS.
  
 D) COMPLETE ALL THE INFORMATION ON TOP OF THE FORM.
 INCLUDING THE BUILDER NAME.
  
 E) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 F) REVISE PAGE 2 OF 5: (1) THERE IS NOT KITCHEN IN THIS
 ADDITION. (2) REVISE FLOOR TYPE AND INSULATION. NEED TO
 CONSIDER THE BATHROOM ADDITION THAT IS NOT ON CONCRETE
 SLAB. (3) TYPE OF ROOF IS NOT HIP ROOF. SEE PLANS AND
 REVISE AS REQUIRED. (4) ATTIC AND CEILING ARE NOT
 VENTED. COORDINATE WITH ARCHITECT AND REVISE AS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712