| Notes |
| Date |
Text |
| 2012-10-10 14:44:53 | PLANS DENIED | | | 1) PROVIDE THE FRESH AIR DUCT SIZE AND | | | FRESH AIR CALCULATIONS ON THE PLANS .PER | | | TABLE 403.3 FBC (M) 2010 | | | 2) PROVIDE A DETAIL FROM THE ENGINEER | | | ON THE CONDENSER TO SLAB TIE DOWN.PER | | | SECTION 301.12 WIND RESISTANCE. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|