Plan Review Notes
Plan Review Notes For Permit 12090413
Permit Number 12090413
Review Stop M
Sequence Number 1
Notes
Date Text
2012-10-10 14:44:53PLANS DENIED
 1) PROVIDE THE FRESH AIR DUCT SIZE AND
 FRESH AIR CALCULATIONS ON THE PLANS .PER
 TABLE 403.3 FBC (M) 2010
 2) PROVIDE A DETAIL FROM THE ENGINEER
 ON THE CONDENSER TO SLAB TIE DOWN.PER
 SECTION 301.12 WIND RESISTANCE.