| Plan Review Notes For Permit 12090413 |
| Permit Number |
12090413 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-28 08:55:15 | 12090413 | | | 3201 SOUTH DIXIE | | | COMMERCIAL RENOVATION | | | | | | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW | | | COMMENTS. | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | | DISCONNECTS AND FOR FLASH PROTECTION AS APPROPRIATE TO | | | THE DESIGN. NEC 110.22, 110.16 | | | | | | VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED | | | WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL | | | SERVICE. NEC 110.26, 240.24 | | | | | | INDICATE THE LOCATION OF THE ELEVATOR PANELBOARD. NEC | | | 215.5 | | | | | | ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | | GFCI PROTECTION. NEC 422.52 | | | | | | RECEPTACLES IN ELEVATOR EQUIPMENT ROOMS AND PITS | | | REQUIRE GFCI PROTECTION. NEC 620.23, 620.85 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|