| 2012-09-28 11:49:23 | BUILDING PLAN REVIEW |
| | PERMIT: 12090357 |
| | ADD: 2421 METROCENTRE BLVD E |
| | CONT: ABAT BUILDERS |
| | TEL: (773)491-3093 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | SEPT. 28/2012 |
| | ACTION: DENIED |
| | |
| | 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS: |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | .2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | .3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | .5. IF BUILDING IS FIRE SPRINKLERED OR NOT? |
| | |
| | 2) 107.3.5.1.( 11) . INTERIOR REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | THE SECTION 804.4.1 WILL REQUIRE KNOWLEDGE OF IF THE |
| | BUILDING IS FIRE SPRINKLERED OR NOT SEE EXCEPTION FOR |
| | CPSC 16CFR, PART 1630. |
| | 804.4.1 MINIMUM CRITICAL RADIANT FLUX. |
| | INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS IN |
| | EXIT ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL |
| | NOT BE LESS THAN CLASS I IN GROUPS I-1, I-2 AND I-3 AND |
| | NOT LESS THAN CLASS II IN GROUPS A, B, E, H, M, R-1, |
| | R-2 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL |
| | COMPLY WITH THE DOCFF-1 "PILL TEST? (CPSC 16 CFR, PART |
| | 1630). |
| | |
| | EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE |
| | PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE |
| | REQUIRED, AND MATERIALS COMPLYING WITH THE DOC FF-1 |
| | "PILL TEST? (CPSC 16 CFR, PART 1630) ARE PERMITTED IN |
| | ANY AREA WHERE CLASS II MATERIALS ARE REQUIRED. |
| | |
| | 3) THE PERMIT APPLICATION INDICATES UNDER THE HEADING |
| | OF DESSCSRIPTION OF WORK WALL SCONCE REPLACEMENT, THERE |
| | IS NO INFORMATION AS TO LOCATION OF WALL SCONCE, |
| | HEIGHTH OF SCONCE NOR HOW FAR FROM THE WALL THE SCONCE |
| | WILL PROTRUDE, PLEASE PROVIVE COMPLIANCE WITH 2010 |
| | FLORIDA ACCESSIBILITY CODE SECTION 307.2 PROTRUSION |
| | LIMITS. |
| | OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM) |
| | AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH |
| | FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM) |
| | MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |