| Plan Review Notes For Permit 12090280 |
| Permit Number |
12090280 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-13 10:29:16 | ROOF-RECOVER BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- ACCORDING TO SEC. 1609.4.3 THIS BUILDING IS LOCATED | | | ON EXPOSURE "C" NOT EXPOSURE "B". ENGINEER NEEDS TO | | | REVISE THE ROOF COMPONENTS AND CLADDING CALCULATIONS | | | AND THE RAS 117 CALCULATIONS AS REQUIRED. | | | | | | 2- ENGINEER CALCULATIONS SUBMITTED SPECIFY ROOF | | | COMPONENTS AND CLADDING FOR GABLE/HIP ROOFS. THIS | | | BUILDING HAS A LOW SLOPE ROOF. CLARIFY AND REVISE AS | | | REQUIRED. SEC. 107.2.1.2 CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|