 633 52ND ST.
 ELECTRIC REPAIR
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN
 ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET
 AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC 210.52
  
 THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 BATH #2 REQUIRES A GROUND FAULT PROTECTED RECEPTACLE.
 NEC 210.52 (D)
  
 THE HALL WAY REQUIRES A RECEPTACLE. NEC 210.52 (H)
  
 PROVIDE AN ELECTRICAL RISER PLAN AND PANEL SCHEDULE.
 NEC 215.5
  