| Plan Review Notes For Permit 12090272 |
| Permit Number |
12090272 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-24 16:52:27 | 12090272 | | | 633 52ND ST. | | | ELECTRIC REPAIR | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN | | | ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET | | | AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC 210.52 | | | | | | THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | | | | BATH #2 REQUIRES A GROUND FAULT PROTECTED RECEPTACLE. | | | NEC 210.52 (D) | | | | | | THE HALL WAY REQUIRES A RECEPTACLE. NEC 210.52 (H) | | | | | | PROVIDE AN ELECTRICAL RISER PLAN AND PANEL SCHEDULE. | | | NEC 215.5 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|