| 2012-12-04 11:40:52 | 3101 OKEECHOBEE BOULEVARD | | | PERMIT #12090235 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ORIGINAL COMMENT:THERE DOES NOT APPEAR TO BE AN | | | EXISTING FIRE BARRIER SEPARATING THE PARTS AREA | | | (STORAGE OCCUPANCY) FROM THE BUSINESS OCCUPANCY. | | | PROVIDE A FIRE BARRIER. ALL OPENINGS AND PENETRATIONS | | | TO BE PROTECTED. | | | | | | ADDITIONAL INFORMATION: NFPA 101 SECTION 39.3.2 - | | | PROTECTION FROM HAZARDS: "HAZARDOUS AREAS INCLUDING, | | | BUT NOT LIMITED TO, AREAS USED FOR GENERAL | | | STORAGE...SHALL BE PROTECTED IN ACCORDANCE WITH SECTION | | | 8.7." | | | | | | NFPA 101 SECTION 8.7.1.1 "PROTECTION FROM ANY AREA | | | HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL TO | | | THE GENERAL OCCUPANCY OF THE BUILDING OR STRUCTURE | | | SHALL BE PROVIDED BY ONE OF THE FOLLOWING MEANS: | | | (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT | | | WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN | | | ACCORDANCE WITH SECTION 8.3 | | | (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING | | | SYSTEMS IN ACCORDANCE WITH SECTION 9.7 | | | (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD | | | IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 | | | THROUGH 43" | | | | | | WESLEY JOLIN | | | WPB FIRE RESCUE | | | OFFICE OF THE FIRE MARSHAL | | | (561) 805 - 6730 | | | [email protected] | | | | | | | | | | | | |
|