2012-09-24 11:18:07****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. INCLUDE WIND DESIGN CRITERIA FBC 1603.4.1.
  
 2. DETAIL FOR TRUSS MODIFICATION (SECTION A-A) NOT
 CLEAR. THE LEFT SIDE SHOWS HGA10, WOOD SCREWS TOP AND
 BOTTOM. THE RIGHT SIDE DETAIL STATES "SECURE TO SUPPORT
 BRACKET WITH USP HGA 10" AND SHOWS AN "EXISTING STEEL
 BRACKET." THE TWO SIDES ARE SHOWN AS IDENTICAL, BUT
 BASED ON THE DRAWING AND LANGUAGE, ONE IS WOOD, THE
 OTHER STEEL? THE HGA10 IS A WOOD TO WOOD CONNECTOR, NO
 CONNECTION INTO STEEL SPECIFIED. PLEASE CLARIFY
 PROPOSED CONSTRUCTION.
  
 3. NO OTHER SUPPORTS OR STRUCTURAL DETAIL PROVIDED
 OTHER THAN THE CONNECTION OF TRUSS TO PLATE OR STEEL
 BRACKET; PLEASE REVISE DETAIL TO INCLUDE TRUSS
 MODIFICATION CONNECTIONS, TOP AND BOTTOM.
  