| 2012-11-08 08:16:12 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | |
| | 1- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. REQ'D BY |
| | COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND |
| | DEVELOPMENT CODE. |
| | |
| | 2- ACCORDING TO CITY RECORDS THIS HOUSE WAS DESIGNED TO |
| | HAVE ROOF SHINGLES. PROVIDE ENGINEERING SHOWING THAT |
| | THE EXISTING HOUSE IS ADEQUATE TO RECEIVE THE |
| | ADDITIONAL CONCRETE TILE LOAD. SEC. 107.2.1.3 CITY |
| | AMENDMENTS TO FBC. (***RESPONSE: ARCHITECT SAID |
| | STRUCTURAL LETTER BY THE ENGINEER. STRUCTURAL LETTER |
| | WAS NOT SUBMITTED). |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQ'D BY DCA |
| | RULE 9N-3 FOR: |
| | |
| | A) CONCRETE TILE. (REPEAT COMMENT. NOT SUBMITTED). |
| | |
| | B) ROOF TILE ADHESIVE. SEE CONCRETE TILE PRODUCT |
| | APPROVAL FOR LISTED ADHESIVES. (REPEAT COMMENT. NOT |
| | SUBMITTED). |
| | |
| | C) ROOF UNDERLAYMENT AS SPECIFIED ON SHEET A2.2. |
| | (REPEAT COMMENT. NOT SUBMITTED). |
| | |
| | D) FLAT ROOF. AND PROVIDE THE RAS 117 CALCULATIONS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF THE |
| | NOA. SIGNED & SEALED IF REQUIRED BY THE NOA. (REPEAT |
| | COMMENT. NOT SUBMITTED). |
| | |
| | E) COLONIAL SHUTTERS AS SHOWN ON PLANS. AND, PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. (REPEAT COMMENT. NOT |
| | SUBMITTED). |
| | |
| | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 5- PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT THE |
| | EGRESS WINDOWS "PGT 24EH" SPECIFIED ON PLANS MEET THE |
| | OPENINGS REQUIREMENTS OF SEC. R310. THIS WINDOW SIZE IS |
| | NOT SHOWN ON NOA 11-1013.14 SUBMITTED. (REPEAT COMMENT. |
| | NOT SUBMITTED). |
| | |
| | 6- PROVIDE ICYNENE MANUFACTURER SPECIFICATIONS TO |
| | VERIFY COMPLIANCE WITH SEC. R316 AND INSULATION R- |
| | VALUE SPECIFIED ON ENERGY CALCULATIONS. (REPEAT |
| | COMMENT. NOT SUBMITTED). |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |