| Plan Review Notes For Permit 12090168 |
| Permit Number |
12090168 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-20 12:15:01 | 12090168 | | | 359 PALMETTO | | | SFD RENOVATION | | | | | | THE SCOPE OF THE ELECTRICAL CHANGES PROPOSED IS NOT | | | CLEAR. PLEASE PROVIDE THE FOLLOWING: | | | | | | PROVIDE AN ELECTRIC SERVICE RISER PLAN WITH PANELS, | | | MAIN BREAKERS, WIRE SIZES, GROUNDING ETC. INDICATE THE | | | LOCATION OF THE SERVICE, DEPTH OF CONDUCTORS ETC. | | | VERIFY THE UNDER GROUND ELECTRICAL SERVICE IS LOCATED | | | MORE THAN 5 FEET FROM THE SWIMMING POOL. SHOW LOCATION | | | OF ALL PANEL BOARDS. NEC 215.15, 680.10 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS. NEC 210.12 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | ALL EXTERIOR RECEPTACLES REQUIRE GROUND FAULT | | | PROTECTION. NEC 210.8 | | | | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|