| 2012-10-05 16:42:08 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS. |
| | CODE: FBC-2010-RESIDENTIAL. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY |
| | COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND |
| | DEVELOPMENT CODE. |
| | |
| | 2- ACCORDING TO CITY RECORDS THIS HOUSE WAS DESIGNED TO |
| | HAVE ROOF SHINGLES. PROVIDE ENGINEERING SHOWING THAT |
| | THE EXISTING HOUSE IS ADEQUATE TO RECEIVE THE |
| | ADDITIONAL CONCRETE TILE LOAD. SEC. 107.2.1.3 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) CONCRETE TILE. |
| | |
| | B) ROOF TILE ADHESIVE. SEE CONCRETE TILE PRODUCT |
| | APPROVAL FOR LISTED ADHESIVES. |
| | |
| | C) ROOF UNDERLAYMENT AS SPECIFIED ON SHEET A2.2. |
| | |
| | D) CUSTOM ENTRY DOOR. NEED TO PROVIDE COMPLETE |
| | ENGINEERING PACKAGE TO APPLY FOR LOCAL PRODUCT APPROVAL |
| | BY ROBERT BROWN. CONTACT HIM AT 805-6652 FOR THE |
| | INFORMATION REQUIRED TO GET THE LOCAL PRODUCT APPROVAL. |
| | |
| | E) GARAGE DOOR AS SHOWN BY ARCHITECT ON PLANS. |
| | |
| | F) FLAT ROOF. AND PROVIDE THE RAS 117 CALCULATIONS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF THE |
| | NOA. SIGNED & SEALED IF REQUIRED BY THE NOA. |
| | |
| | G) COLONIAL SHUTTERS AS SHOWN ON PLANS. AND, PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. |
| | |
| | H) PLASTPRO FLORIDA PRODUCT APPROVAL FL15180.1 |
| | SUBMITTED FOR SINGLE OUTSWING IMPACT DOOR DOESN'T MEET |
| | THE SIZE OF DOOR SHOWN ON PLANS BY THE ARCHITECT. |
| | |
| | I) PLASTPRO FLORIDA PRODUCT APPROVAL FL15180.4 |
| | SUBMITTED FOR DOUBLE OUTSWING IMPACT DOORS DOESN'T MEET |
| | THE SIZE OF DOOR SHOWN ON PLANS. AND, CLARIFY WHERE IS |
| | THIS DOOR GONG TO BE INSTALLED?. SEE PLANS. |
| | |
| | J) PLASTPRO FLORIDA PRODUCT APPROVAL FL15180.3 |
| | SUBMITTED FOR SINGLE DOOR WITH SIDELITES DOESN'T MEET |
| | THE SIZE OF DOOR SHOWN ON PLANS. AND, CLARIFY WHERE IS |
| | THIS DOOR GOING TO BE INSTALLED?. |
| | |
| | K) PLASTPRO FLORIDA PRODUCT APPROVAL FL15180.11 |
| | SUBMITTED FOR SINGLE FIBERGLASS DOOR DOESN'T MEET THE |
| | SIZE OF DOOR SHOWN ON PLANS. AND, CLARIFY WHERE IS THIS |
| | DOOR GOING TO BE INSTALLED. |
| | |
| | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 5- SHEET D1.1: NOTE ON THE NORTH WEST CORNER STATES |
| | "REMOVE EXISTING STORAGE SHED ROOF ONLY - WALL AND SLAB |
| | TO REMAIN". NEED TO PROVIDE MORE INFORMATION. HOW IS |
| | THE ROOF GOING TO BE REBUILT. ALSO, COORDINATE WITH |
| | ZONING COMMENTS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 6- PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT THE |
| | EGRESS WINDOWS "PGT 24EH" SPECIFIED ON PLANS MEET THE |
| | OPENINGS REQUIREMENTS OF SEC. R310. THIS WINDOW SIZE IS |
| | NOT SHOWN ON NOA 11-1013.14 SUBMITTED. |
| | |
| | 7- SPECIFY SIZE OF ATTIC ACCESS. ALSO, SHOW THAT ATTIC |
| | ACCESS IN STORAGE ROOM BY THE FAMILY/DINING ROOM |
| | PROVIDES THE REQUIRED HEIGHT REQUIRED BY SEC. R807. |
| | |
| | 8- PROVIDE ICYNENE MANUFACTURER SPECIFICATIONS TO |
| | VERIFY COMPLIANCE WITH SEC. R316 AND INSULATION R- |
| | VALUE SPECIFIED ON ENERGY CALCULATIONS. |
| | |
| | 9- SHEET S3.0: |
| | A) DESIGN LOAD SCHEDULE: SPECIFY ALL DESIGN LOADS AS |
| | REQUIRED BY SEC. R301.1 AND TABLE R301.5. INCLUDE THE |
| | ATTIC LIVE LOAD AND SPECIFY STORAGE OR NON STORAGE. |
| | |
| | B) UPDATE FLORIDA PRODUCT APPROVAL NUMBERS SPECIFIED ON |
| | THE TRUSS CONNECTOR SCHEDULE. FL1901 AND FL474 ARE NOT |
| | APPROVED FOR THE 2010 FBC VERSION. |
| | |
| | 10- ARCHITECT TO PROVIDE IN THE TITLE BLOCK AL THE |
| | INFORMATION REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| | ADMINISTRATIVE CODE. NEED FIRM'S LICENSE NUMBER AND |
| | NAME OF ARCHITECT SIGNING THE PLANS. SEC. 107.1 CITY |
| | AMENDMENTS. |
| | |