| 2012-09-26 14:35:57 | BUILDING PLAN REVIEW |
| | PERMIT: 12090138 |
| | ADD: 444 W RAILROAD AVE 5TH FL. |
| | CONT: TBD |
| | TEL: (561)###-#### |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | SEPT. 26/ 2012 |
| | ACTION: DENIED |
| | |
| | 1) SHEET LS1.1 GENERAL BUILDING DATA, BUILDING TYPE IS |
| | INDICATED AS A IIIB PLEASE RECLASSIFY THE BUILDING. |
| | THIS BUILDING WAS BUILT UNDER THE 2001 FBC-B AND WAS |
| | CLASSIFIED AS MINIMUM BUILDING TYPE II, UNDER THE 2010 |
| | CODE THE BUILDING IS CLASSIFIED AS A IB SEE CODE |
| | CONVERSIONS 2001 TO 2004 FBC. |
| | |
| | 2) SHEET LS1.1 LIFE SAFETY SHEET IS MISSING CERTAIN |
| | CODE CRITERIA: |
| | 2010 FBC-B 107.3.5.1.1(6) OCCUPANCY LOAD/ EGRESS |
| | CAPACITY AT DOORS AND STAIRS, TABLE 1004.1.1. |
| | |
| | 3) SHEET A1.1 INDICATES A WALL TYPE TAG AS A WT-5 FOR |
| | ALL TENANT SEPERATION WALLS THAT ARE COMMON TO ELEVATOR |
| | LOBBY 521 & 530. SHEET A4.2 WALL TYPES ONLY INDICATE |
| | WALL TAG TYPE WT-6 AS A 1 HDOORR FIRE RATED WALL. 2010 |
| | FBC-B 709.1(6) REQUIRES A 1 HOUR FIRE RATING. |
| | MECHANICAL SHEETS INDICATE FIRE RATED DAMPERS IN THESE |
| | WALLS AS WELL. |
| | |
| | 4) SHEET A1.1 FIFTH FLOOR DOORS 27 & 28 DOORS IN SERIES |
| | PLEASE REVIEW 2010 ACCESSIBILITY CODE SECTION 404.2.6 |
| | DOORS IN SERIES REQUIRE 48" BETWEEN DOORS AND THERE |
| | SWING. |
| | |
| | 5) A1.6 INDICATES A SECURE PARKING SLIDING GATE HOW |
| | WILL THE FIRE DEPARTMENT GAIN ENTRANCE IN CASE OF |
| | EMERGENCY? |
| | |
| | 6) A1.7 SOUTH STAIR TOWER , NOTE DEA ANTENNAS CAN NOT |
| | HAVE CABLEING GOING THROUGH THE STAIR TOWER PER 2010 |
| | FBC-B 1022.4 PENETRATIONS. |
| | |
| | 7) SHEET A-3.1 BREAKROOM # 515 & 516 INDICATE THE SINK |
| | TO BE AT A MAXIMUM HEIGHT OF 3'-0". PLEASE REVIEW |
| | SECTION 2010 FBC-ACCESSIBILTY CODE 606.3. |
| | |
| | 8) SHEET A-3.2 GRAB BAR DETAIL MEASURES THE HEIGHT OF |
| | THE GRAB BARS FROM THE FLOOR TO THE CENTER LINE OF THE |
| | BAR, THERE WAS A CHANGE IN THE 2010 ACCESSIBLTY CODE |
| | WHERE THE MEASUREMENT IS TAKEN TO THE TOP OF GRAB BARS, |
| | SECTION 609.4. |
| | |
| | JAMES A. WITMER CBO |