| 2012-11-01 16:46:00 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2010 |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PAGE M2.1.1: AT STAIR A-1 ENTRANCE, FLOOR PLAN SHOWS |
| | TWO FIRE DAMPERS IN LOCATIONS WHERE WALLS NO LONGER |
| | EXIST. THE DESIGN INTENT IS UNCLEAR. PLEASE CLARIFY AND |
| | SHOW FIRE DAMPERS IN THEIR PROPER LOCATION PER FBC-M |
| | 607.8 AND FBC-B 106.1. |
| | |
| | 2. PAGE M2.1.1: KEY NOTES 1 AND 2 CALL FOR DUCT |
| | PENETRATIONS OF THE FLOOR/CEILING ASSEMBLY BETWEEN THE |
| | 4TH AND 5TH FLOORS. SHOW HOW THESE PENETRATIONS OF THIS |
| | RATED ASSEMBLY ARE TO BE PROTECTED PER FBC-M 607.5. |
| | |
| | 3. PAGE M2.1.1: SEVERAL AREAS INVOLVING EVIDENCE |
| | STORAGE ARE SHOWN ON LIFE SAFETY PLAN TO HAVE FIRE |
| | RESTSTANCE RATED WALLS. NONE OF THE DUCT PENETRATIONS |
| | OR TRANSFER OPENINGS IN THESE AREAS ARE SHOWN TO BE |
| | PROTECTED. SHOW HOW THESE PENETRATIONS AND TRANSFER |
| | OPENINGS ARE TO BE PROTECTED PER FBC-M 607.5. |
| | |
| | 4. PAGE M2.1.2: WEAPONS CLEANING ROOM 423 SHOWS AN |
| | EXHAUST FAN ABOVE THE CEILING IN THE PLENUM SPACE. |
| | EXHAUST DUCT UNDER POSITIVE PRESSURE (DISCHARGE SIDE OF |
| | FAN) SHALL NOT BE LOCATED IN A RETURN AIR PLENUM PER |
| | FBC-M 601.5. SHOW HOW THIS DUCT IS TO BE ISOLATED FROM |
| | THE PLENUM SPACE (RETURN AIR COULD BE ELIMINATED FROM |
| | THIS ROOM, WITH CEILING SPACE ISOLATED FROM THE |
| | PLENUM). |
| | |
| | 5. PAGE M0.1: OUTSIDE AIR CALCULATIONS SHOW TRAINING |
| | AREA WITH AN OCCUPANT LOAD OF 24 PERSONS WHILE THE |
| | FLOOR PLAN SHOWS AT LEAST 67 SEATS IN THIS SPACE. |
| | PROVIDE A CALCULATION SHOWING THE ACTUAL OCCUPANT LOAD |
| | OF THIS SPACE PER FBC-M SECTION 403. |
| | |