2012-09-11 16:11:00FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET A-2 - THE MENS AND WOMENS RESTROOMS APPEAR NOT
 TO MEET THE 2010 ACCESSIBILTY CODE. PLEASE SEE SECTION
 604.3.2 FOR WATER CLOSET CLEARANCE (THE STALLS WOULD BE
 REQUIRED TO BE A MINIMUM OF 7'-1" WIDE TO ACHIEVE THE
 REQUIRED 5' CLEAR SPACE FOR THE WATER CLOSET), SECTION
 202.4.1 FOR DISPROPORTIONATE COST, AND SECTION 202.4.2
 FOR ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 ***NOTES***
 1. PLUMBING DRAWINGS ARE OK
  
 2. FUEL GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE
 APPLICATION, PLAN, REVIEW, FEES, AND PERMIT REQUIRED.
  
 3. SHEET C-1: THE FBC CODE EDITION FOR THIS PROJECT IS
 FBC 2010
  