| Plan Review Notes For Permit 12090097 |
| Permit Number |
12090097 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-09 13:31:11 | PLANS DENIED | | | 1) SEPARATE APPLICATION, PLANS AND PERMIT REQUIRED | | | FOR HOOD FIRE SYSTEM. | | | 2) PROVIDE THE SIZE RODS USED FOR HANGING THE HOOD | | | ON THE PLANS. PROVIDE TWO COPIES OF THE INSTALLATION | | | INSTRUCTIONS FOR THE 3M WRAP WITH THE RESUBMITTELS. | | | PER SECTION 107 FBC 2010 | | | 3) THE DETAIL ON THE HOOD FIRE SYSTEM NOTES ON THE | | | PULL STATION SAY 6 FT. AWAY .REFER TO SECTION 904.11.1 | | | MANUAL SYSTEM OPERATION.MINIMUM 10 FT. MAX. 20 FT. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | | | | |
|