Plan Review Notes
Plan Review Notes For Permit 12090097
Permit Number 12090097
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-09-08 17:54:57871 VILLAGE
 PERMIT #12090097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A CORRECT ADDRESS ON THE PLANS. CROSS-CHECK THE
 ADDRESS WITH THE ASSOCIATED WITH THE PCN NUMBER.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL COOKING EQUIPMENT (#11, 12, 17,20) CAPABLE OF
 PRODUCING GREASE LADEN VAPORS OR SMOKE SHALL BE LOCATED
 UNDER A TYPE 1 COMMERCIAL HOOD PROTECTED BY A WET
 CHEMICAL SUPPRESSION SYTEM.
  
 EXIT DOOR #1 AND #2 APPEAR TO BE LOCATED TOO CLOSE TO
 ONE ANOTHER TO BE CLASSIFIED AS SEPARATE EXITS. IN
 BUILDINGS PROTECTED THROUGHOUT BY A SPRINKLER SYSTEM,
 THE MINIMUM SEPARATION DISTANCE BETWEEN TWO EXITS OR
 EXIT ACCESS DOORS SHALL BE NOT LESS THAN ONE-THIRD THE
 LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA BEING SERVED. REFERENCE SECTION
 7.5.1.3.3 OF FLORIDA FIRE PREVENTION CODE - NFPA 101.
  
 CUSTOMERS ARE NOT PERMITTED TO BE ROUTED THROUGH A
 KITCHEN AREA TO ACCESS AN EXIT.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE KITCHEN HOOD
 SUPPRESSION SYTEMS, FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  