| 2012-10-18 07:50:14 | BUILDING PLAN REVIEW |
| | PERMIT: 12090076 |
| | ADD: 931 VILLAGE BLVD # 901 |
| | CONT: PM BUILDERS |
| | TEL: (954)916-2655 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) PROVIDE SHOP DRAWINGS BEFORE FRAMING INSPECTION . |
| | SHEET A1 & A2 REFRENECE MAGNETIC SHIELDING DESIGN BY |
| | UNIVERSAL SHIELDING, PLEASE PROVIDE COMPLIANCE WITH |
| | 2010 FBC-B: |
| | 435.13.5.1 SHIELDING. |
| | EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY |
| | PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN |
| | INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS |
| | OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64E-5, |
| | FLORIDA ADMINISTRATIVE CODE. |
| | 435.5.1.1 |
| | STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL |
| | BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND |
| | WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7 |
| | FEET (2.1 M). |
| | 435.5.1.2 |
| | DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL |
| | HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT |
| | REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE |
| | INSTALLED. |
| | |
| | ------------------------------------------------------- |
| | ---------------------------------------------- |
| | PRODUCT APPROVALS SUBMITTED FOR EXTERIOR GLAZING; |
| | FL# 12522.1 YKK AP IMPACT "35H DG OUTSWING ENTRANCE |
| | DOOR +/- 90 |
| | FL# 14218.3 YKK AP IMACT "YHS-50" DG AL FLUSH GLAZED |
| | STOREFRONT +/- 65.0 |
| | ANCHOR SPACING +/- 57.6 |
| | DOOR MULLION 120X 72 +/- 77.3 |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |