| Date |
Text |
| 2012-09-25 13:44:11 | 901 VILLAGE BOULEVARD - SUITE #702 |
| | PERMIT #12090076 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE ADDRESS PROVIDED ON THE PLANS (901 VILLAGE) DOES |
| | NOT MATCH THE ADDRESS PROVIDED ON THE PERMIT |
| | APPLICATION (931 VILLAGE). |
| | |
| | PROVIDE A SUITE NUMBER IN THE TITLEBLOCK INFORMATION. |
| | |
| | INDICATE THE PREVIOUS USE/OCCUPANCY OF THIS SUITE. |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED AND SHALL HAVE "NO SMOKING" SIGNS |
| | POSTED. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE |
| | ALARM SYSTEM. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | ALL EXTERIOR DOORS NOT FUNCTIONING AS EXITS SHALL BE |
| | PERMANENTLY MARKED AND CLEARLY INDICATED AS, "NOT AN |
| | EXIT." |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |