 PLEASE ADDRESS THE FOLLOWING PLAN REVIEW COMMENTS.
  
 VERIFY THE INDICATED FAULT CURRENT CAPACITY OF THE
 ELECTRIC SERVICE AND SWITCH GEAR IS ADEQUATE. NEC
 110.9, 110.10
  
 VERIFY THE EXISTING SERVICE GUTTER IS ADEQUATELY SIZED
 FOR THE NEW SERVICE CONDUCTORS. NEC 366.22, 366.56
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT. NEC 110.22, 110.16
  
 PROVIDE AN ADDITIONAL NOTE ON THE POWER PLAN WHICH
 INDICATES ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRE A
 SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT
 GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT
 GROUND . NEC 517.13
  
 FEEDERS TO PANELS A AND P APPEAR TO BE INCORRECTLY
 SIZED. NEC 215.5
  
 MDP 2 REQUIRES A MAIN DISCONNECT OR MAIN BREAKER. NEC
 240.21
  
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
  
 VERIFY X-RAY ROOMS WILL HAVE REQUIRED SAFETY WARNING
 DEVICES, SIGNS, WARNING LIGHTS AND ELECTRICAL
 INTERLOCKS. FBC 435.9
  
 PROVIDE A LIGHTING DENSITY SUMMARY VERIFYING COMPLIANCE
 WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC EC 505.5.3
  
  