| Plan Review Notes For Permit 12090076 |
| Permit Number |
12090076 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-27 11:37:21 | 12090076 | | | 931 VILLAGE BLVD. #702 | | | MEDICAL OFFICE | | | | | | PLEASE ADDRESS THE FOLLOWING PLAN REVIEW COMMENTS. | | | | | | VERIFY THE INDICATED FAULT CURRENT CAPACITY OF THE | | | ELECTRIC SERVICE AND SWITCH GEAR IS ADEQUATE. NEC | | | 110.9, 110.10 | | | | | | VERIFY THE EXISTING SERVICE GUTTER IS ADEQUATELY SIZED | | | FOR THE NEW SERVICE CONDUCTORS. NEC 366.22, 366.56 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | | EQUIPMENT. NEC 110.22, 110.16 | | | | | | PROVIDE AN ADDITIONAL NOTE ON THE POWER PLAN WHICH | | | INDICATES ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRE A | | | SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT | | | GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT | | | GROUND . NEC 517.13 | | | | | | FEEDERS TO PANELS A AND P APPEAR TO BE INCORRECTLY | | | SIZED. NEC 215.5 | | | | | | MDP 2 REQUIRES A MAIN DISCONNECT OR MAIN BREAKER. NEC | | | 240.21 | | | | | | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 | | | | | | VERIFY X-RAY ROOMS WILL HAVE REQUIRED SAFETY WARNING | | | DEVICES, SIGNS, WARNING LIGHTS AND ELECTRICAL | | | INTERLOCKS. FBC 435.9 | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY VERIFYING COMPLIANCE | | | WITH THE 2010 FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC EC 505.5.3 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|