Plan Review Notes
Plan Review Notes For Permit 12090076
Permit Number 12090076
Review Stop B
Sequence Number 1
Notes
Date Text
2012-09-10 14:10:20BUILDING PLAN REVIEW
 PERMIT: 12090076
 ADD: 931 VILLAGE BLVD # 901
 CONT: PM BUILDERS
 TEL: (954)916-2655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 SEPT. 10/2011
 ACTION: DENIED
  
 1) SHEET A-1 NOTE "N" INDICATES THE DEMOLITION OF A
 PORTION OF WALL, BUT NO INFORMATION IS PROVIDED FOR THE
 REBUILDING OF BLOCK WALL, WILL NEW COLUMNS BE REQUIRED,
 CELLS GROUTED, HORIZONTAL 2010 FBC-B 2101.2.2 STRENGTH
 DESIGN.
  
 2) SHEET A-4 INDICATES NEW STOREFRONT WINDOWS, MULLIONS
 & DOORS. 1609.1.2 PROTECTION OF OPENINGS. GLAZED
 OPENINGS IN BUILDINGS LOCATED IN WIND-BORNE DEBRIS
 REGIONS SHALL BE PROTECTED FROM WIND-BORNE DEBRIS.
 GLAZED OPENING PROTECTION FOR WIND-BORNE DEBRIS SHALL
 MEET THE REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM
 E 1996, ANSI/DASMA 115 (FOR GARAGE DOORS AND ROLLING
 DOORS) OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED
 THEREIN.
 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF
 GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST OF ASTM E 1996.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (E) SHUTTERS
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) SHEET A1 & A2 REFRENECE MAGNETIC SHIELDING DESIGN BY
 UNIVERSAL SHIELDING, PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-B:
 435.13.5.1 SHIELDING.
  
 EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY
 PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN
 INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS
 OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64E-5,
 FLORIDA ADMINISTRATIVE CODE.
 435.5.1.1
  
 STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL
 BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND
 WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7
 FEET (2.1 M).
 435.5.1.2
  
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL
 HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT
 REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE
 INSTALLED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved