Plan Review Notes
Plan Review Notes For Permit 12090027
Permit Number 12090027
Review Stop E
Sequence Number 1
Notes
Date Text
2012-09-06 15:59:56THE FOLLOWING INFORMATION HAS BEEN APPLIED TO THE PLAN.
  
 ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN
 ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET
 AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC 210.52
 THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER