| Plan Review Notes For Permit 12090027 |
| Permit Number |
12090027 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-06 15:59:56 | THE FOLLOWING INFORMATION HAS BEEN APPLIED TO THE PLAN. | | | | | | ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN | | | ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET | | | AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC 210.52 | | | THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|