| 2012-10-03 13:01:25 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) FLAT ROOF. AND: CLEARLY IDENTIFY APPROVED ASSEMBLY |
| | TO BE INSTALLED. PROVIDE RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL. IF GENERAL LIMITATION REQUIRES THOSE |
| | CALCULATIONS TO BE SIGNED AND SEALED, THEN, PROVIDE |
| | SIGNED AND SEALED RAS 117 CALCULATIONS. |
| | |
| | B) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | C) WINDOW MULLIONS AS SHOWN ON PLANS. |
| | |
| | D) ENTRY DOOR WITH SIDELITES AND TRANSOM ABOVE AS SHOWN |
| | ON PLANS. |
| | |
| | E) 2'-8" X 7'-0" SINGLE CASEMENT WINDOW AS SHOWN ON |
| | PLANS. PRODUCT APPROVAL SUBMITTED DOESN'T INCLUDE THIS |
| | WINDOW SIZE. |
| | |
| | F) DOUBLE FRENCH DOORS WITH SIDELITES AS SHOWN ON |
| | PLANS. |
| | |
| | G) SINGLE AND DOUBLE FRENCH DOORS AS SHOWN ON PLANS. |
| | NOA 08-0821.09 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. |
| | VISIT THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. |
| | RESUBMIT. |
| | |
| | H) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ARCHITECT ON SHEET A-3. |
| | |
| | 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | 4- PROVIDE 2 COPIES OF SOIL TEST REPORT. ONLY ONE COPY |
| | WAS SUBMITTED. SEC. 107.3.1 CITY AMENDMENTS. |
| | |
| | 5- VERIFY/CLARIFY IF ATTIC ACCESS SHOWN ON "SAM'S |
| | CLOSET" AND ON "HIS CLOSET" COMPLY WITH THE HEADROOM |
| | REQUIREMENTS OF SEC. R807. |
| | |
| | 6- SHEET A-4: |
| | A) REVISE ROOF SHEATHING "NAILING PATTERN SCHEDULE".. |
| | ACCORDING TO SEC. R803.2.3.1 THE MIN. TYPE OF NAIL TO |
| | BE USED IS 8D RING SHANK NAILS. THIS INCLUDE ROOF ZONES |
| | 2 AND 3. REVISE AS REQUIRED. |
| | |
| | B) REVISE "ROOF COMPONENTS AND CLADDING PRESSURES". |
| | THEY DON'T CORRESPOND TO EXPOSURE "D". SEE TABLE |
| | R301.2(2) INCLUDING ALL THE FOOTNOTES. |
| | NOTE: REMEMBER THAT TABLE R301.2(2) IS FOR EXPOSURE |
| | "B". AND, THE DESIGN PRESSURES FOR CORNER AND PERIMETER |
| | AREAS ARE HIGHER BECAUSE OF THE ROOF PITCH (3 1/2 SHOWN |
| | ON ELEVATIONS). |
| | |
| | 7- PROVIDE MANUFACTURER'S SPECS FOR THE ICYNENE TO BE |
| | USED AND THE 1" RIGID INSULATION TO VERIFY COMPLIANCE |
| | WITH THE ENERGY CALCULATIONS REQUIREMENTS AND SEC. |
| | R316. |
| | |
| | 8- PROVIDE DRAINAGE PLANS SHOWING COMPLIANCE WITH SEC. |
| | R401.3. WATER CAN'T BE DIVERTED TO NEIGHBORS PROPERTY |
| | EITHER. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |