| Plan Review Notes For Permit 12090015 |
| Permit Number |
12090015 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-05 16:53:54 | 12090015 | | | 412 CLEMATIS STREET #412 | | | FIELD OF GREENS | | | | | | PROVIDE A DESIGNATED LOCATION FOR THE PANEL BOARDS | | | WHICH REMAINS CLEAR OF OBSTRUCTION AND STORAGE AT ALL | | | TIMES. INCLUDE A RISER PLAN SHOWING THE EXISTING | | | ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECTS. NEC | | | 110.26, 215.5, 240.24 | | | | | | PROVIDE A DETAIL VERIFYING THE REQUIRED WORKING | | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | | PROVIDED FOR THE ELECTRICAL PANEL BOARDS. NEC 110.26, | | | 240.24, 408.17 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|