2012-09-10 16:57:01RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- FLAT ROOF:
  
 A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE FLAT ROOF TO BE INSTALLED. SEC.
 107.2.1.2 CITY AMENDMENTS TO FBC.
  
 B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED TO MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF 2010
 FLORIDA RESIDENTIAL CODE.
  
 C) IF PRODUCT APPROVAL SUBMITTED REQUIRES SIGNED AND
 SEALED RAS 117 CALCULATIONS. THEN, NEED TO PROVIDE THE
 SIGNED AND SEALED RAS 117 CALCULATIONS. SEC. 107.2.1.2
 CITY AMENDMENTS TO FBC.
  
 2- ROOF SHINGLES NOA 09-0825.06 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA. RESUBMIT TWO COPIES OF
 CURRENT NOA. SEC. 107.2.1.2 CITY AMENDMENTS TO FBC.
  