| 2012-09-13 16:43:35 | 12090010 | | | 223 CLEMATIS STREET | | | SIGN FOR BOBBI SUE BBQ | | | | | | PROVIDE ELECTRICAL SIGN DETAIL SHOWING REQUIRED | | | DISCONNECTS AND CIRCUIT SIZE. DISCONNECTS ARE REQUIRED | | | WITHIN SIGHT OF THE SIGN FACE AND SIGN CONTROLLER. NEC | | | 600.6 | | | | | | VERIFY AND INDICATE ON THE PLANS THAT THE SIGN HAS A | | | LISTING BY A NATIONALLY RECOGNIZED TESTING LABORATORY. | | | NEC 110.3, 600.3 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|