| Plan Review Notes For Permit 12080975 |
| Permit Number |
12080975 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-07 12:41:14 | DATE: 09/07/12 WAITING FOR THE ELECTRONIC FILES IN | | | PROJECTDOX TO BE AVAILABLE SO SPRINKLER SHOP DRAWINGS | | | CAN BE CHECKED AGAINST ENGINEERING DRAWINGS FOR | | | COMPLIANCE. | | | | | | | | | 4801 DREHER TRAIL NORTH | | | PERMIT #12080975 | | | MASTER #12020414 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | DATE:09/25/12 | | | | | | THE ENGINEERING CONSTRUCTION DDOCUMENTS ALREADY | | | ESTABLISH J. SMITH AS THE ENGINEER OF RECORD FOR THE | | | FIRE SPRINKLER SYSTEM; THEREFORE, THE FIRE SPRINKLER | | | SHOP DRAWINGS AND HYDRAULIC CALCULATIONS SHALL NOT BE | | | SIGNED OR SEALED. | | | | | | SHEET F-001 OF THE CONSTRUCTION DOCUMENTS INDICATE THE | | | PERMANENT EXHIBIT AREA AND TRAVELING EXHIBIT AREAS | | | SHALL BE DESIGNED AS ORDINARY HAZARD, GROUP II WITH A | | | DESIGN DENSITY OF 0.20 GPM/SQ.FT. THE SHOP DRAWINGS | | | INDICATE THESE AREAS ARE LIGHT HAZARD. | | | | | | CONFIRM WITH THE ENGINEER OF RECORD THAT EXTENDED | | | COVERAGE SPRINKLER ARE AN ACCEPTABLE ALTERNATIVE TO THE | | | STANDARD SPRAY SPRINKLERS. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|