2012-09-28 16:46:14RESIDENTIAL (R3) ALTERATION/RENOVATION PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- WASHER DRAIN AND LAVATORY CAN'T BE ON THE SAME STACK
 AS SHOWN ON THE PLUMBING RISER DIAGRAM. SEE SEC.
 P3005.1.1 AND REVISE AS REQUIRED.
  
 2- CLEAN OUT IS NOT SHOWN PROPERLY. SEE SEC. P3005.2.6
 AND REVISE AS REQUIRED.
  