| 2012-09-28 16:43:39 | RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOFING CONTRACTOR APPLIED FOR A ROOFING PERMIT. |
| | NEED PRODUCT APPROVAL FOR THE FLAT ROOF. AND, CLEARLY |
| | SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE |
| | INSTALLED. ALSO, PROVIDE RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL. SEE LAST PAGE OF NOA. IF GENERAL |
| | LIMITATION #7 REQUIRES SIGNED AND SEALED RAS 117 |
| | CALCULATIONS. THEN, NEED TO PROVIDE SIGNED AND SEALED |
| | RAS 117 CALCULATIONS. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE |
| | ENGINEER ON ALL DETAILS AND WALL SECTIONS. PROVIDE ONLY |
| | THE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| | SPECIFIED CONNECTOR. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE ALL PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | 3- SHOW COMPLIANCE WITH THE EGRESS REQUIREMENTS |
| | REQUIRED BY SEC. R310 FOR SECOND FLOOR BEDROOM WINDOW. |
| | WINDOW SPECIFIED IS S.H. 34" X 53". THIS WINDOW SIZE IS |
| | NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED. IS |
| | THIS A CUSTOM SIZED WINDOW?. PROVIDE MANUFACTURER'S CUT |
| | SHEETS SHOWING COMPLIANCE WITH THE EGRESS OPENINGS |
| | (HEIGHT, WIDTH AND TOTAL MINIMUM OPENING AREA OF |
| | 5.7S.F.). |
| | |
| | 4- ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C" NOT "B". REVISE DESIGN |
| | PARAMETERS ON SHEET A-1 AND DOORS AND WINDOWS DESIGN |
| | PRESSURES ON SHEET A-2 AS REQUIRED. OR ENGINEER MAY |
| | SPECIFY AN INTERMEDIATE EXPOSURE BY PROVIDING A |
| | COMPLETE RATIONAL ANALYSIS AS ALLOWED BY THE EXCEPTION |
| | ON SEC. R301.2.1.4. |
| | |
| | 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | DWELLING/GARAGE FIRE SEPARATION AS REQUIRED BY TABLE |
| | R302.6. |
| | |
| | 6- SHEET A-1: |
| | A) REVISE ROOF SHEATHING NOTE SHOWN ON THE GENERAL |
| | CONSTRUCTION NOTES. ROOF ZONE #3 REQUIRES 8D RING SHANK |
| | NAILS AT 4" O.C. AS REQUIRED BY SEC. R803.2.3.1. |
| | |
| | B) REVISE STAIR SPECIFICATIONS TO COMPLY WITH SEC. |
| | R311.7.4. THE NOSING IS NOT OPTIONAL. SEE SEC. |
| | R311.7.4.2 TO SEE HOW THE TREAD IS MEASURED AND REVISE |
| | AS REQUIRED. |
| | |
| | C) REVISE DESIGN PARAMETERS. THIS IS NOT ALTERATION |
| | LEVEL I. SEE SEC. 405 OF 2010 FBC-EXISTING BUILDING AND |
| | REVISE AS REQUIRED. |
| | |
| | 7- SHEET A-2: REVISE DESIGN PRESSURES FOR THE GARAGE |
| | DOORS. PROVIDE DESIGN PRESSURES FOR GARAGE DOOR SIZE AS |
| | SHOWN ON PLANS. PROVIDE DESIGN PRESSURES AS REQUIRED BY |
| | SEC. R301.2.1.4.3. |
| | |
| | 8- SHEET S-1: |
| | A) REVISE STAIR SPECIFICATIONS. SEE ITEM #7(B) ABOVE. |
| | |
| | B) PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF THE RAILING/GUARDRAIL TO SHOW |
| | COMPLIANCE WITH TABLE R301.5. |
| | |
| | C) PROVIDE COMPLETE SPECIFICATIONS FOR THE TYPE AND |
| | NUMBER OF SCREWS FOR THE 2X WOOD DECK AND THE 2X4 |
| | LEDGERS RECEIVING THE STAIR STRINGERS. SEC. 107.2.1 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | D) PROVIDE MANUFACTURER SPECIFICATIONS FOR RIGID 3/4" |
| | FOAM INSULATION SHOWING COMPLIANCE WITH THE R-19 VALUE |
| | SPECIFIED ON WALL SECTION 2/S-2. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |