| Plan Review Notes For Permit 12080919 |
| Permit Number |
12080919 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-01-23 09:48:13 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS | | | REQUIRED BY FBCR M1401.3 (REPEAT COMMENT) | | | | | | 2) SUBMIT TWO SETS OF MECHANICAL PLANS WITH THE | | | LOCATIONS AND SIZES OF ALL SUPPLY AND RETURN DUCTS | | | SPECIFIED. SPECIFY THE GRILL SIZES FOR THE SUPPLIES AND | | | RETURNS AND THE CFMS FOR EACH OF THE SUPPLY OUTLETS. | | | CITY AMENDMENTS 107.3.5.3 (REPEAT COMMENT) | | | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT IS | | | COORDINATED WITH THE SIZING CALCULATIONS. FBCR M1401.3 | | | (REPEAT COMMENT) | | | | | | 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | | RETURN AIR REQUIREMENTS ON THE PLANS. (REPEAT COMMENT) | | | | | | 5) SPECIFY THE NAME AND LICENSE NUMBER OF THE PERSON | | | RESPOSIBLE FOR THE DESIGN OF THE HVAC SYSTEM ON THE | | | PLANS. CITY AMENDMENTS 107.3.4 AND FBC FS481.229 & | | | 471.003 (NEW COMMENT) | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|