| Notes |
| Date |
Text |
| 2012-08-28 14:30:51 | REQUESTED ADDITIONAL INFORMATION ON THE SERVICE DESIGN | | | FROM THE CONTRACTOR. | | | | | | PROVIDE FAULT CURRENT CAPABILITES FOR THE ELECTRIC | | | SERVICE. NWEC 110.9 | | | SHOW ALL WIRE AND CONDUIT SIZED. NEC 215.5 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS REVIEW | | | 561-805-6718 |
|