Plan Review Notes
Plan Review Notes For Permit 12080871
Permit Number 12080871
Review Stop E
Sequence Number 2
Notes
Date Text
2012-08-28 14:30:51REQUESTED ADDITIONAL INFORMATION ON THE SERVICE DESIGN
 FROM THE CONTRACTOR.
  
 PROVIDE FAULT CURRENT CAPABILITES FOR THE ELECTRIC
 SERVICE. NWEC 110.9
 SHOW ALL WIRE AND CONDUIT SIZED. NEC 215.5
  
 ROBERT LECKY
 ELECTRIC PLANS REVIEW
 561-805-6718