| 2012-12-06 14:01:52 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW COMMENTS |
| | CODE: 2010 FBC. |
| | |
| | 1- REVISE ENERGY CALCULATIONS SUBMITTED (SEC. 103.2 OF |
| | 2010 FBC-ENERGY CONSERVATION). COORDINATE ALL THE |
| | INFORMATION WITH PLANS AND PRODUCT APPROVALS SUBMITTED: |
| | (NOTE: SEE SEC. 101.4.3 OF 2010 FBC-ENERGY |
| | CONSERVATION. COMPLIANCE CAN BE ACHIEVED FOR THE |
| | ADDITION ALONE OR FOR ENTIRE BUILDING). |
| | |
| | A) COMPLETE ALL THE INFORMATION ON TOP OF FORM. |
| | |
| | B) SPECIFY ALL WALL TYPES AS SHOWN ON PLANS. THERE ARE |
| | NOT CONCRETE BLOCK WALLS. SEE PLANS. AND PROPERTY |
| | APPRAISAL SAYS WOOD FRAME STUCCO/HOLLOW TILE. |
| | |
| | C) SPECIFY ALL CEILING TYPES AS SHOWN ON PLANS. |
| | |
| | D) CLARIFY WHY THE EF VALUE FOR THE HOT WATER SYSTEM IS |
| | "0". |
| | |
| | E) CLEARLY PROVIDE THE NAME OF PERSON DOING THE |
| | CALCULATIONS AS REQUIRED BY SEC. 405.4.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | F) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM. |
| | |
| | G) ROOF SPECIFICATION ON SHEET 2 OF 6 TO MATCH PLANS. |
| | THERE ARE FLAT ROOFS AND ACCORDING TO CITY RECORDS THEY |
| | HAVE CLAY TILE NOT FLAT CONCRETE TILE. |
| | |
| | H) REVISE THE ATTIC INFORMATION ON SHEET 2 OF 6. THERE |
| | ARE VENTED AND UNVENTED ATTICS. |
| | |
| | I) REVISE WALL ON SHEET 3 OF 6. THERE ARE MASONRY WALLS |
| | AND FRAMED WALLS. |
| | |
| | J) THERE ARE NO WOOD DOORS. SEE PLANS AND PRODUCT |
| | APPROVALS SUBMITTED. REVISE PAGE 3 OF 6. |
| | |
| | 2- FLAT ROOF NOA 12-0227.18 SUBMITTED. A) SELECTED |
| | ASSEMBLY ON PAGE 6 OF 7 IS FOR AN INSULATED ASSEMBLY. |
| | ARCHITECTURAL PLANS DON'T SPECIFY INSULATED ASSEMBLY. |
| | COORDINATE WITH ARCHITECT AND REVISE AS REQUIRED. |
| | (REPEAT COMMENT. ARCHITECT IS NOT SPECIFYING INSULATED |
| | ASSEMBLY AS SHOWN ON NOA SUBMITTED). |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR FRENCH DOORS AS SHOWN ON PLANS. |
| | INCLUDING FRENCH DOORS WITH SIDELITES AS SHOWN ON |
| | PLANS. |
| | ***RESPONSE: NOA 11-1025.02 SUBMITTED WAS SUPERSEDED BY |
| | MIAMI-DADE. VISIT MIAMI-DADE WEBSITE AND DOWNLOAD |
| | CURRENT NOA. RESUBMIT. |
| | |
| | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS. (REPEAT |
| | COMMENT). |
| | ***RESPONSE: ONLY THE SIMPSON STRUCTURAL CONNECTORS |
| | WERE APPROVED BY THE ENGINEER. ALL THE PRODUCT |
| | APPROVALS NEED TO BE REVIEWED AND APPROVED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |