| Plan Review Notes For Permit 12080803 |
| Permit Number |
12080803 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-13 10:43:49 | PLANS DENIED | | | 1) ENERGY CALCULATIONS AND PLANS DO NOT MATCH. | | | PLANS SHOW A/C # 1 AND 3 56200 BTU AND A/C # 2 1950 | | | BTU. | | | ENERGY CALCULATION SHOW A/C 1,2 56000 AND A/C 3 1950 | | | BTU. | | | 2) DETAIL #2 NO PAGE M2.01 PROVIDE LAG BOLT SIZE FOR | | | CONDENSER STAND. | | | 3) REFER TO SECTION 604.4.1 SUPERVISION 2010 FBC (M) | | | 4) PROVIDE PRODUCT APPROVAL FOR OUTDOOR LOUVER | | | PER SECTION 107.3.4 GENERAL 2010 FBC | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | |
|