Plan Review Notes
Plan Review Notes For Permit 12080803
Permit Number 12080803
Review Stop M
Sequence Number 1
Notes
Date Text
2012-09-13 10:43:49PLANS DENIED
 1) ENERGY CALCULATIONS AND PLANS DO NOT MATCH.
 PLANS SHOW A/C # 1 AND 3 56200 BTU AND A/C # 2 1950
 BTU.
 ENERGY CALCULATION SHOW A/C 1,2 56000 AND A/C 3 1950
 BTU.
 2) DETAIL #2 NO PAGE M2.01 PROVIDE LAG BOLT SIZE FOR
 CONDENSER STAND.
 3) REFER TO SECTION 604.4.1 SUPERVISION 2010 FBC (M)
 4) PROVIDE PRODUCT APPROVAL FOR OUTDOOR LOUVER
 PER SECTION 107.3.4 GENERAL 2010 FBC
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  