2012-09-05 16:46:54BUILDING PLAN REVIEW
 PERMIT: 12080803
 ADD: 120 S OLIVE AVE SUITE # 105
 CONT: ANDERSON-MOORE CONSTRUCTION
 TEL: (561)662-1819
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET SP1 PROJECT DATA INDICATES THIS TO BE A TYPE
 IIIB BUILDING, 2010 FBC-B TABLE 503 FOR A A2
 OCCUPANCYWITH BUSSINESS OCCUPANCIES ABOVE ONLY ALLOWS
 FOR A UILDING HEIGHT OF 3 STORIES WITH A STORY INCREASE
 FOR A FULLY SPRINKLERED BUILDING. THIS BUILDING IS A
 MINIMUM OF 7 STORIES TALL, PLEASE CORRECT TTHE MINIMUM
 BUILDING TYPE.
  
 2) THIS BUILDING IS ALSO A CONDOMINIUM ASSOCATION,
 SHEET SP-1 INDICATES THERE ARE TWO TENANT SPACES THAT
 ARE BEING COMBINED INTO ONE TENANTCY, A UNITY OF TITLE
 WILL BE REQUIRED. UNITY OF TITLE. THE PROPOSED BUILDING
 STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE
 LOTS WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF
 TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 3) SHEET A1.0 WITH AN OCCUPANT LOAD OF 50 OCCUPANTS OR
 MORE THE EXISTING FRONT DOOR SWINGS THE WRONG WAY, 2010
 FBC-B 1008.1.2. PLEASE PROVIDE ON THIS PLAN THE
 LOCATION OF THE PROPERTY LINE, OUTSWING DOORS CAN'T
 SWING OUT OVER THE PROPERTY LINE. 2010 FBC-B 3202.2.
  
 4) SHEET A1.0 DOOR SCHEDULE INDICATES THE FRONT DOOR
 HAS EXISING FIRE HARDWARE PLEASE PROVIDE COMPLIANCE
 WITH SECTION 2010 FBC-B 1008.1.10.
  
 5) SHEET A1.0 THE BACK EXIT INTO A ENCLOSED EXIT
 PASSAGE WAY THAT OPENS TO AN EGRESS COURT THAT LEADS TO
 A PUBLIC ALLEY, IS THIS AREA USED FOR STORAGE AND OR
 USE OF ICE MAKERS OR OTHER EQUIPMENT? 1027.1(1.1)-(1.3)
 , 1027.6 ACCESS TO A PUBLIC WAY. THE EXIT DISCHARGE
 SHALL PROVIDE A DIRECT AND UNOBSTRUCTED ACCESS TO A
 PUBLIC WAY. IS THERE A CLEAR PATH WITH NO OBSTRUCTIONS,
 GATES TO THE PUBLIC ALLEY?
  
 6) SHEET A1.0 ACCESSIBLE RESTROOM DETAIL INDICATES THE
 DIMENSIONS TO THE CENTERLINE, PLEASE NOTE IN THE NEW
 2010 ACCESSIBLITY CODE THESE MEASUREMENTS ARE TAKEN TO
 THE TOP OF THE GRAB BARS 2010 FBC-ACCESSIBILITY CODE
 609.3.
  
 7) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 803.1.1
 INTERIOR WALL AND CEILING FINISH MATERIALS.
  
 8) SHEET A1.0 PLAN NOTE # 6 INDICATES THE PROJECT IS
 LOCATED WITHIN THE HVHZ, ONLY BROWARD & DADE COUNTIES
 ARE CONSIDERED TO BE THE HIGH VELOCITY HURRICANE ZONE.
 WITH COMMENT NUMBER (3) PRODUCT APPROVALS WILL BE
 REQUIRED FOR THE REPLACEMENT OF THE FRONT ENTRY DOOR(
 1715.5.3) , IF GLAZED THEN PROTECTION OF GLAZED
 OPENINGS IN ACCORDANCE WITH 1609.1.2.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 9) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) SHEET A2.0 DOES NOT INDICATE EXISTING FIRE
 SPRINKLERS LOCATED WITHIN THE EXIT PASSAGEWAY, PLEASE
 REVIEW SECTION 2010 FBC-B 1027.1.EXCEPTION 1.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved