| 2012-09-25 11:09:12 | RESIDENTIAL (R3) REPAIRS MECHANICAL REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- REVISE EQUIPMENT SIZING CALCULATIONS. COORDINATE | | | WITH ARCHITECTURAL PLANS FOR TOTAL AIR CONDITIONED AREA | | | AND REVISE CALCULATIONS AS REQUIRED. SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | 2- SHEET A-3: | | | A) SPECIFY SIZES OF ALL THE TRANSFER DUCTS AND GRILLES | | | TO VERIFY COMPLIANCE COMPLIANCE WITH THE BALANCED | | | RETURN AIR SEC. M1602.4 OF 2010 FBC-RESIDENTIAL CODE. | | | | | | B) CLARIFY HOW IS THE LANAI AREA GOING TO BE AIR | | | CONDITIONED. NOT GRILLES SHOWN ON THIS AREA AND THERE | | | ARE PLENTY OF WINDOWS ON THIS AREA. SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|