Plan Review Notes
Plan Review Notes For Permit 12080772
Permit Number 12080772
Review Stop M
Sequence Number 1
Notes
Date Text
2012-09-25 11:09:12RESIDENTIAL (R3) REPAIRS MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS. COORDINATE
 WITH ARCHITECTURAL PLANS FOR TOTAL AIR CONDITIONED AREA
 AND REVISE CALCULATIONS AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- SHEET A-3:
 A) SPECIFY SIZES OF ALL THE TRANSFER DUCTS AND GRILLES
 TO VERIFY COMPLIANCE COMPLIANCE WITH THE BALANCED
 RETURN AIR SEC. M1602.4 OF 2010 FBC-RESIDENTIAL CODE.
  
 B) CLARIFY HOW IS THE LANAI AREA GOING TO BE AIR
 CONDITIONED. NOT GRILLES SHOWN ON THIS AREA AND THERE
 ARE PLENTY OF WINDOWS ON THIS AREA. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712