| 2012-09-21 15:57:13 | RESIDENTIAL (R3) REPAIRS BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- SHEET A-0: |
| | A) ACCORDING TO SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL CODE THIS BUILDING IS LOCATED ON |
| | EXPOSURE "D" NOT "C". ARCHITECT TO REVISE THE BUILDING |
| | EXPOSURE AND THE DOORS AND WINDOWS DESIGN PRESSURES. |
| | |
| | B) ARCHITECT TO REVISE THE WIND SPEED INFORMATION. |
| | SPECIFY THE ULTIMATE DESIGN WIND SPEED ( 170 MPH VULT) |
| | AND THE NOMINAL DESIGN WIND SPEED (132 MPH VASD). SEC. |
| | R301.2.1.3. |
| | |
| | C) ARCHITECT TO REVISE THE INFORMATION SHOWN ON THE |
| | "PROJECT DATA". ACCORDING TO PLANS SUBMITTED THERE IS |
| | NOT ADDITION SHOWN. ALSO, THE CONSTRUCTION TYPE IS NOT |
| | CONSTRUCTION TYPE IV. SEE SEC. 602.5 OF FBC-BUILDING |
| | CODE AND REVISE AS REQUIRED. |
| | |
| | D) AIR CONDITIONED SQUARE FOOTAGE SHOWN ON THE BUILDING |
| | AREA DOESN'T MATCH AIR CONDITIONED SQUARE FOOTAGE SHOWN |
| | ON THE ENERGY CALCULATIONS. COORDINATE AS REQUIRED TO |
| | MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 2- SHEET A-1: |
| | A) REVISE GENERAL NOTE #2. SPECIFY THE CURRENT CODE IN |
| | EFFECT AND REVISE THE WIND SPEED. SEE ITEM # 1(B) |
| | ABOVE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) ROOF NOTE #1 STATES THAT ROOF TRUSSES ARE TO BE |
| | REMOVED AND REPLACED. PROVIDE ROOF FRAMING PLAN AND |
| | TRUSS ANCHOR SCHEDULE. TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.2.1.4.3. |
| | |
| | C) PROVIDE ROOF SHEATHING FASTENING SPECIFICATIONS. |
| | INCLUDE NAILING TYPE AND SPACING FOR ROOF ZONE #3 AS |
| | REQUIRED BY SEC. R803.2.3.1. |
| | |
| | D) FLOOR PLAN: CLARIFY HOW TO ENTER BEDROOM #1 AND #2. |
| | THERE IS A WALL BLOCKING THE ENTRANCE. CLARIFY WHAT ARE |
| | THE ARROWS SHOWN ON THE MASTER BEDROOM CLOSET SHOWN |
| | FOR?. CLARIFY WHAT ARE THE LINES SHOWN ON THE WEST SIDE |
| | WINDOW OF THE LANAI SHOWN FOR?. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | E) PROVIDE SIZES OF WINDOWS AND DOORS TO VERIFY |
| | COMPLIANCE WITH THE ENERGY CALCULATIONS. SEC. 107.2.1 |
| | CITY AMENDMENTS AND SEC. 405.5 OF FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED: |
| | A) PROVIDE CORRECT ADDRESS. THIS IS NOT 29TH STREET. |
| | SEC. 405.4.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | B) REVISE CONDITIONED FLOOR AREA. COORDINATE WITH ITEM |
| | #1D ABOVE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) WINDOW MULLIONS AS SHOWN ON PLANS. |
| | |
| | B) ROOF SHINGLES. FLORIDA PRODUCT APPROVAL FL5444-R3 |
| | SUBMITTED IS FOR THE 2007 BUILDING CODE. NEED CURRENT |
| | 2010 CODE. |
| | |
| | C) TRUSSES STRUCTURAL CONNECTORS SPECIFIED BY THE |
| | ARCHITECT FOR THE NEW TRUSSES. PROVIDE ONLY THE PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR. |
| | |
| | 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 6- FLAT ROOF PRODUCT APPROVAL: PROVIDE SIGNED AND |
| | SEALED RAS 117 CALCULATIONS FOR THE NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7 ON LAST PAGE OF THE FLAT ROOF NOA |
| | 08-0410.09 SUBMITTED. NEED CALCULATIONS TO MEET THE |
| | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. |
| | |
| | 7- SPECIFY SIZE OF WINDOWS FOR BEDROOM #1 TO VERIFY |
| | COMPLIANCE WITH EGRESS REQUIREMENTS SEC. R310 AND SEC. |
| | 601.2 AND SEC. 604.1 OF 2010 FBC-EXISTING BUILDING |
| | CODE. SPECIFY SIZE AND TYPE OF EXISTING WINDOW TO BE |
| | REPLACED AND PROPOSED WINDOW. WHAT'S THERE A SINGLE |
| | WINDOW REPLACED WITH 2 WINDOWS MULLED TOGETHER. THIS |
| | WILL REDUCE THE SIZE OPENING FROM THE WINDOW. |
| | THEREFORE, MAKING THE OPENING SMALLER THAN IT WAS. |
| | |
| | 8- NEW TRUSSES. THEREFORE NEW ROOF: |
| | A) PROVIDE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE ATTIC VENTILATION SEC. R806. |
| | |
| | B) PROVIDE DETAILS AND SPECIFICATIONS FOR ATTIC ACCESS |
| | TO SHOW COMPLIANCE WITH SEC. R807. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |