| Plan Review Notes For Permit 12080740 |
| Permit Number |
12080740 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-10-15 13:31:58 | REVISION REQUIRED | | | | | | 1) SPECIFY WHICH ONE OF THE ASSEMBLIES FROM THE | | | HYDRO-STOP PREMIUM COAT SYSTEM PRODUCT APPROVAL THAT | | | WAS SUBMITTED WILL BE INSTALLED. ALL THREE OF THE | | | ASSEMBLIES REQUIRE A MECHANICALLY FASTENED INSULATION | | | BASE LAYER TO WHICH THE PREMIUM COAT SYSTEM IS APPLIED. | | | THE MAXIMUM DESIGN PRESSURE LISTED IN THE NOA IS -60 | | | PSF WHICH DOES NOT MEET THE HIGHER UPLIFT PRESSURES AT | | | THE PERIMETER AND CORNER AREAS. THE STRUCTURE IS | | | LOCATED IN 170 MPH VULT / 132 VASD EXPOSURE C PER FBC | | | R301.2.1.4. PLEASE SUBMIT 2 SETS OF RAS 117 | | | CALCULATIONS FOR THE ENHANCED FASTENING OF THE | | | INSULATION THAT HAVE BEEN SIGNED AND SEALED BY A | | | FLORIDA ENGINEER, ARCHITECT OR REGISTERED ROOF | | | CONSULTANT AS REQUIRED BY LIMITATION NUMBER 7. | | | FBCR301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|