| 2012-08-27 10:29:36 | 12080707 | | | 700 S. ROSEMARY AVENUE # 100 | | | MELLOW YELLOW BUILD OUT | | | | | | PLEASE CLARIFY THE ELECTRICAL RISER PLAN AS NOTED. | | | | | | DISTRIBUTION PANEL ?LDP? AND PANEL ?LP1? MAY BE | | | MISLABELED. NEC 215.5 | | | | | | ?LP1 / LDP? REQUIRE A MAIN BREAKER. NEC 408.36 | | | | | | INDICATE THE SIZE OF THE XFMR. PROVIDE LINE AND LOAD | | | FEEDER CONDUCTOR SIZES. NEC 215.5 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|