| 2012-08-23 18:57:42 | BUILDING PLAN REVIEW | | | PERMIT: 12080707 | | | ADD: 700 S ROSEMARY AVE SUITE # 100 | | | CONT: TO BE DETERMINED | | | TEL: (561)856-6655 NEYITA | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | BUILDING PROVISOS: | | | | | | 1) SHEET A2.5 DETAILS 1 & 2 AND SHEET A5.3 DETAILS 1 & | | | 2 THE DESIGNER OF RECORD TO PROVIDE TYPE OF FASTENERS | | | TO BE INSTALLED FOR THE DECORATIVE FEATURES TO THE | | | STRUCTURE ABOVE, PROVIDE SPACING, AND TYPE OF ANCHORS | | | BY THE TIME OF FRAMING INSPECTION. 2010 FBC-B 2506.2 | | | STEEL STUDS NON-LOAD BEARING. | | | | | | 2) UPDATE PLANS SHEET A0.2 HANDICAPPED RESTROOMS ARE | | | MISSING THE REQUIRED LAVATORY IN THE STALL, SHEET A4.3 | | | DETAIL # 1 INDICATES LAVATORY IN STALL. 2010 FBC-B | | | 604.8.1.6. | | | | | | 3) FIRE SPRINKLER PLANS ARE REQUIRED TO BE SUBMITTED, | | | TO UPDATE CHANGE OF HEAD LOCATION PER 2010FBC-B | | | 107.3.51.1(5) | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | |
|