| Plan Review Notes For Permit 12080699 |
| Permit Number |
12080699 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-24 16:35:36 | SEE NOTE ON PLANS: | | | | | | MINIMUM 22 KIC REQUIRED FOR SERVICE EQUIPMENT. NEC | | | 110.9 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS REVIEW | | | 561-805-6718 | | | | | | |
|