Plan Review Notes
Plan Review Notes For Permit 12080685
Permit Number 12080685
Review Stop P
Sequence Number 1
Notes
Date Text
2012-08-27 13:52:482010 FBC
  
 DENIED BY PLUMBING
  
 1) FBCR P3108.2 STATES THAT NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION. THE TWO
 SHOWERS IN THE MASTER BATHS AND THE SHOWER AND WATER
 CLOSET IN BATH #3 DISCHARGE UPSTREAM OF THE DRY-VENTED
 LAVATORIES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]