| Plan Review Notes For Permit 12080685 |
| Permit Number |
12080685 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-08-28 16:37:55 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES A SOIL BEARING REPORT IN | | | ACCORDANCE WITH FBC R401.4. | | | | | | 2) SUBMIT TWO SETS OF A SURFACE DRAINAGE PLAN SHOWING | | | COMPLIANCE WITH FBC R401.3. | | | | | | 3) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED | | | BY FBC ENERGY CONSERVATION SECTION 401.2. | | | | | | 4) SHOW COMPLIANCE WITH FBCR G2407.5 FOR THE REQUIRED | | | INDOOR COMBUSTION AIR FOR THE CLOTHES DRYER IN THE | | | UTILITY ROOM. | | | | | | 5) ON SHEET A901, NOTE 1 UNDER EXTERIOR WINDOW AND DOOR | | | GENERAL NOTES REFERENCES THE 2007 FBC AND A 140 MPH | | | WIND SPEED. PLEASE CORRECT TO 2010 FBC AND 170 MPH WIND | | | SPEED. | | | | | | 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 5' X | | | 8' FIXED GLASS WINDOWS IN THE LIVING ROOM. THESE | | | WINDOWS ARE LARGER THAN THE MAXIMUM SIZE ALLOWED BY THE | | | PRODUCT APPROVAL THAT WAS SUBMITTED. DCA RULE 9N-3 | | | | | | 7) PRODUCT APPROVALS WERE SUBMITTED FOR PROJECTED ( | | | AWNING ) WINDOWS NOA #11-1110.17. THERE WERE NOT ANY OF | | | THIS WINDOW TYPE SPECIFIED ON THE PLANS. IT APPEARS | | | THESE MAY HAVE BEEN SUBMITTED FOR THE CASEMENT WINDOWS. | | | SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE CASEMENT | | | WINDOWS. DCA RULE 9N-3 | | | | | | 8) TO FACILITATE THE PLAN REVIEW PROCESS, PLEASE | | | PROVIDE A RESPONSE LETTER INDICATING HOW EACH REVIEW | | | ITEM WAS ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|