| Date |
Text |
| 2012-10-04 15:22:59 | 6751 NORTH JOG ROAD | | | PERMIT #12080615 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE LOCKING KNOX CAPS ON THE FIRE DEPARTMENT | | | CONNECTION. | | | | | | PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW | | | SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO | | | THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER | | | ACTIVATES IN THE ELEVATOR MACHINE ROOM. | | | | | | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND | | | END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE | | | PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE | | | LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE | | | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING | | | UPWARD MOVEMENT. | | | | | | INDICATE THE HYDROSTATIC PRESSURE THAT THE SYSTEM | | | PIPING WILL NEED TO BE TESTED AT FOR EACH FLOOR. | | | | | | NOTE: THE SKYWALK BRIDGE INFORMATION HAS NOT BEEN | | | SUBMITTED. SPRINKLER PROTECTION MAY BE NEEDED PER FBC | | | SECTION 3104 WHICH IS DEPENDENT UPON EXIT TRAVEL | | | DISTANCES AND % OPENNESS OF THE SKYWALK BRIDGE. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | OFFICE OF THE FIRE MARSHAL | | | [email protected] | | | (561) 805 - 6730 |
|