2012-10-04 15:22:596751 NORTH JOG ROAD
 PERMIT #12080615
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE LOCKING KNOX CAPS ON THE FIRE DEPARTMENT
 CONNECTION.
  
 PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW
 SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO
 THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER
 ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 INDICATE THE HYDROSTATIC PRESSURE THAT THE SYSTEM
 PIPING WILL NEED TO BE TESTED AT FOR EACH FLOOR.
  
 NOTE: THE SKYWALK BRIDGE INFORMATION HAS NOT BEEN
 SUBMITTED. SPRINKLER PROTECTION MAY BE NEEDED PER FBC
 SECTION 3104 WHICH IS DEPENDENT UPON EXIT TRAVEL
 DISTANCES AND % OPENNESS OF THE SKYWALK BRIDGE.
  