Plan Review Notes
Plan Review Notes For Permit 12080534
Permit Number 12080534
Review Stop E
Sequence Number 1
Notes
Date Text
2012-08-20 08:16:44PLEASE OBSERVE THE FOLLOWING CONDITIONS PLACED ON THE
 PLANS.
  
 PROVISO:
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR NEW
 GENERAL PURPOSE OUTLETS. NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER