2012-08-21 13:22:442010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF ENERGY CALCULATIONS SHOWING
 COMPLIANCE WITH FBC ENERGY CONSERVATION CHAPTER 4.
  
 2) SHOW COMPLIANCE WITH FBC R310.1 FOR EMERGENCY ESCAPE
 AND RESCUE OPENINGS IN BEDROOMS NUMBER 1 AND 2.
  
 3) CLARIFY THE ROOF FRAMING OVER THE AREA BETWEEN THE
 FLORIDA ROOM AND THE EXISTING BATH SHOWN ON SHEET 2.1.
 EXPLAIN HOW THE TRUSSES ARE SUPPORTED AT THE OUTER
 ENDS.
  
 4) UNDER THE DESIGN PARAMETERS ON SHEET 1.1 PLEASE
 UPDATE THE EDITION OF ASCE 7 TO ASCE 7-10 WHICH IS THE
 ONE REFERENCED IN THE 2010 FBCR. FBCR CHAPTER 43.
  
 5) ON SHEET 3.1 THE COMPONENT AND CLADDING PRESSURE
 ZONE TABLE LISTS 140 MPH. THE WINDSPEED FOR WEST PALM
 BEACH IS 170 MPH VULT AND 132 VASD. FBC R301.2.1 &
 R301.2.1.3
  
 6) ON SHEET 4.1 THE TYPICAL GABLE END SECTION
 REINFORCEMENT TABLE SPECIFIES 140 MPH. PLEASE CORRECT.
 FBC R301.2.1 & R301.2.1.3
  
 7) THE WALL SECTION ON 3.1 AND 4.2 SPECIFY R-19 CEILING
 INSULATION. THE SECTION ON 4.1 HAS R-30. PLEASE
 COORDINATE THE R-VALUES ON THE PLANS WITH THE ENERGY
 CALCULATIONS. FBC ENERGY CONSERVATION CHAPTER 4
  
 8) THE DESIGNER OF RECORD FOR THE PROJECT IS REQUIRED
 TO REVIEW AND APPROVE THE PRODUCT APPROVALS IN WRITING.
 CITY AMENDMENTS 107.3.4.1
  
 9) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ROOF
 SHINGLES AS REQUIRED BY DCA RULE 9N-3.
  
 10) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SINGLE
 HUNG WINDOWS SPECIFIED ON THE PLANS. THE PRODUCT
 APPROVALS THAT WERE SUBMITTED ARE FOR HORIZONTAL
 SLIDING WINDOWS. DCA RULE 9N-3.
  
 11) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 GLAZED FRENCH DOORS ARE NOT IMPACT RATED AND REQUIRE
 IMPACT PROTECTION IN ACCORDANCE WITH FBC R301.2.1.2.
 SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE STORM
 PANELS THAT WILL BE USED ON THE SINGLE AND DOUBLE
 FRENCH DOORS. SPECIFY THE ATTACHMENT SYSTEM FROM THE
 PRODUCT APPROVAL THAT WILL BE USED. INCLUDE THE
 MOUNTING OPTION, THE FASTENER TYPE AND SPACING, SPAN
 AND GLASS CLEARANCE REQUIREMENTS.
  
 12) THE PLANS WILL BE REQUIRED TO HAVE AN IMPACT FEE
 REVIEW BY PALM BEACH COUNTY. THE STAMPED PLANS AND A
 COPY OF THE PAID RECEIPT WILL BE REQUIRED TO BE
 SUBMITTED BEFORE THE PERMIT IS ISSUED.
  
 13) IN ORDER TO SPEED THE REVIEW PROCESS, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS
 WERE ADDRESSED.
  