Plan Review Notes
Plan Review Notes For Permit 12080523
Permit Number 12080523
Review Stop B
Sequence Number 1
Notes
Date Text
2012-08-16 10:02:462010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WHICH
 REQUIRES THE LOWEST FINISHED FLOOR AND EQUIPMENT TO BE
 LOCATED AT OR ABOVE THE MINIMUM ELEVATION OF 7'6" BFE
 (BASE FLOOD ELEVATION). THIS INCLUDES THE 6" FREEBOARD
 ESTABLISHED BY THE CITY OF WEST PALM BEACH'S FLOOD
 ORDINANCE. SPECIFY THE FINISH FLOOR ELEVATIONS FOR THE
 EXISTING STRUCTURE AND THE PROPOSED ELEVATOR AND
 EQUIPMENT ON THE PLANS AND SUBMIT A ELEVATION
 CERTIFICATE FOR THE PROPOSED EQUIPMENT. WPB CODE OF
 ORDINANCES CHAPTER 94, ARTICLE XVII SECTIONS 94-541
 THRU 94-547.(LESS THAN SUBSTANTIAL IMPROVEMENT)
  
 2) THE PLANS INDICATE THAT THE SERVICE STAIRS ARE TO BE
 DEMOLISHED SO THAT THE ELEVATOR CAN BE INSTALLED SO
 THAT THE EXISTING FLOOR OPENING FOR THE STAIR CAN BE
 USED. SHOW COMPLIANCE WITH FBC R311.4 WHICH REQUIRES
 VERTICAL EGRESS FROM THE SECOND FLOOR BUY A STAIRWAY IN
 ACCORDANCE WITH SECTION R311.7 ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]