2012-08-28 09:29:07PROVIDE AN ELECTRICAL WIRING DIAGRAM FOR THE NEW AC
 SYSTEM. SHOW THE NEW ELECTRICAL CIRCUITS, DISCONNECTS,
 WIRE SIZES AND OVERCURRENT PROTECTION. INDICATE THE
 SIZE AND LOCATION OF THE EXISTING ELECTRICAL PANEL
 BOARD. NEC 215.5
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER