| Plan Review Notes For Permit 12080493 |
| Permit Number |
12080493 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-11-07 13:59:55 | 12080493 | | | 255 WALTON BLVD. | | | MULTIFAMILY RENOVATION | | | | | | THE FOLLOWING NEC CODE REQUIREMENTS WERE NOTED ON THE | | | PLAN. | | | | | | MINIMUM WIRE SIZE FOR 100 AMP FEEDER IS # 3 COPPER. NEC | | | T. 310.16 | | | MINIMUM WIRE SIZE FOR 400 AMP SERVICE IS 500 KCMIL | | | COPPER. NEC T 310.16 | | | BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH CIRCUIT. | | | NEC 210.11 (C) (3) | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|