| 2012-08-22 11:54:46 | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. SHEET A1-102, A1-201 |
| | THE DETAIL FOR THE STANDARD TOILET STALLS DOES NOT HAVE |
| | A MEASUREMENT FOR STALL DEPTH ON THE DRAWING. THE |
| | INSIDE DIMENSION APPEARS TO BE 4'-6". THE MINIMUM FOR |
| | STALLS IS 60" DEEP. FBC PLUMBING 405.3.1 |
| | |
| | 2. AS THREE FLOORS ARE OCCUPIED AND AN AGGREGATE OF |
| | MORE THAN SIX WATER CLOSETS ARE REQUIRED, A UNISEX |
| | RESTROOM WILL BE REQUIRED. THE RESTROOM SHOULD BE |
| | PLACED ON THE SECOND FLOOR TO BE WITHIN ONE FLOOR LEVEL |
| | PER 403.3.2. THE UNISEX FIXTURES COUNT AS REQUIRED |
| | FIXTURES. |
| | 403.5 UNISEX TOILET AND BATHING ROOMS. |
| | IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE |
| | UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE |
| | OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS |
| | REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE |
| | WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE |
| | OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET |
| | ROOM REQUIREMENT. |
| | |
| | 3. SHEET PB-106 |
| | THE SANITARY DRAINAGE FROM THE SECOND FLOOR RESTROOMS |
| | IS DROPPING INTO THE VENT FOR THE FIRST FLOOR |
| | RESTROOMS. |
| | 908.1 INDIVIDUAL VENT AS COMMON VENT. |
| | AN INDIVIDUAL VENT IS PERMITTED TO VENT TWO TRAPS OR |
| | TRAPPED FIXTURES AS A COMMON VENT. THE TRAPS OR TRAPPED |
| | FIXTURES BEING COMMON VENTED SHALL BE LOCATED ON THE |
| | SAME FLOOR LEVEL. |
| | |
| | 4. A CLEANOUT WILL BE REQUIRED NEAR THE BASE OF THE |
| | SOIL STACK FOR THE SECOND FLOOR RESTROOMS. |
| | 708.3.4 BASE OF STACK. |
| | A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH WASTE |
| | OR SOIL STACK. |
| | |
| | 5, ALL HOSE BIBBS AND WALL HYDRANTS REQUIRE A SEPARATE |
| | SHUTOFF VALVE. |
| | 606.2 LOCATION OF SHUTOFF VALVES. |
| | SHUTOFF VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER THAN |
| | ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| | |
| | 6. SHEET PB-106 |
| | THE DOWNFEED WATER RISERS FOR THE FIRST FLOOR REQUIRE |
| | SHUTOFF VALVES. |
| | 606.1 LOCATION OF FULL-OPEN VALVES. |
| | FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN |
| | OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL |
| | OCCUPANCIES. |
| | |
| | 7. A SERVICE SINK WAS NOT FOUND ON THE PLAN. |
| | 403.1 ASSEMBLY OCCUPANCIES REQUIRE A SERVICE SINK. |
| | |
| | 8. SHEET PB-102 |
| | A. A SHUTOFF VALVE IS REQUIRED WHERE THE DOMESTIC WATER |
| | ENTERS THE BUILDING. 606.1 (2) |
| | B. A BACKFLOW PREVENTOR IS SHOWN INSIDE THE BUILDING. |
| | IF THIS IS THE MAIN RPZ BACKFLOW FOR THE BUILDING, IT |
| | SHOULD BE AS CLOSE TO THE DOMESTIC WATER METER AS |
| | POSSIBLE PER UTILITIES ORD. |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |
| | FAX # 805-6676 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |